GE DS200PTBAG1BBA Mark V Terminal Board

  • Manufacturer: GE
  • Product Number: DS200PTBAG1BBA
  • Condition: New & In Stock
  • Product Type: Mark V Terminal Board
  • Origin: USA
  • Payment Methods: T/T, Western Union
  • Dimensions: 260 × 100 × 25 mm
  • Weight: 0.39 kg
  • Shipping Port: Xiamen, China
  • Lead Time: 1-3 Working Days
  • Warranty: One Year
  • Certificate: COO
  • Courier partners: DHL, UPS, TNT, FedEx and EMS.

Product Detail

Contact Us

FAQS

Packing & Delivery

Company Information
e-mail [email protected]
Mobile +8615305023276
Whatsapp +8615305023276
WeChat 15305023276
Add to Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China

Technical Specifications

Parameter Specification
Model DS200PTBAG1BBA
Brand GE
Product Series Mark V
Product Type Terminal Board
Functional Acronym PTBA
Functional Description Protection Termination Module
Board Type Multi-input and multi-output termination board
Main Application Mark V Speedtronic turbine control system
Main Function Signal termination, field wiring connection and protective signal interface
Typical Protection Functions Overspeed protection and flame detection
Terminal Connections Screw terminal connections numbered 1 to 79
Pin Header Connectors 4 vertical pin header connectors
Other Connectors Multiple vertical pin connectors
Protection Components Metal oxide varistors, capacitors and resistors
Configuration Components Jumper switches
Mounting Factory-drilled mounting holes
Board Identification Board ID and wiring/connection identification markings
System Integration Interfaces field signals with the Mark V control system
Typical Application Gas turbines, steam turbines and industrial turbine control systems
Dimensions 260 × 100 × 25 mm
Weight 0.39 kg

FAQ

1. What is the main function of the GE DS200PTBAG1BBA Mark V Terminal Board?
The DS200PTBAG1BBA is a terminal board used in GE Mark V Speedtronic turbine control systems. Its primary role is to provide a structured interface between field wiring and the turbine control system. The board accommodates multiple signal connections and provides termination points for different protection and control circuits. It is associated with protective functions such as overspeed protection and flame detection, while also providing the required electrical termination for field signals. The board includes connectors, terminal blocks, passive components, protective components, and jumper locations that allow it to integrate with the surrounding Mark V control architecture.

2. What types of signals can be connected through the DS200PTBAG1BBA?
The DS200PTBAG1BBA is designed to handle multiple field signal connections associated with turbine control and protection functions. Depending on the specific Mark V application and system configuration, these connections can include signals related to protective inputs, overspeed detection, flame detection, generator measurements, synchronization, and other turbine control circuits. The exact signal assignment depends on the specific control cabinet wiring and application configuration. Before replacing or rewiring the board, the original terminal assignments should be carefully documented because changing a field connection to an incorrect terminal can cause incorrect signal interpretation or interfere with turbine protection functions.

3. What is the role of the PTBA functional designation on this board?
PTBA identifies the functional role of the board within the Mark V control system. The board is used as a protection termination interface, providing termination points and signal routing between field devices and the appropriate control or protection circuitry. The functional designation helps technicians identify the board’s position and purpose within the larger turbine control architecture. Because Mark V systems can contain multiple terminal and control boards with different functions, identifying the correct board designation is important during maintenance and replacement. The DS200PTBAG1BBA should therefore be matched according to its complete part number rather than only the general PTBA designation.

4. How should the DS200PTBAG1BBA be handled during installation or replacement?
The board should be handled using appropriate electrostatic discharge protection procedures because it contains electronic components that can be damaged by static electricity. Before removing or installing the board, the relevant turbine control equipment should be placed in a safe maintenance condition and power isolation procedures should be followed according to the plant’s maintenance requirements. Field wiring should be clearly identified and documented before disconnection. During installation, connectors and terminal wiring must be positioned correctly without excessive mechanical force. After installation, technicians should carefully verify all terminal connections, jumpers, connectors, and board identification before restoring the system to operation. Functional testing should then be performed to confirm that the associated control and protection signals operate correctly.

5. What should be checked if signals connected to the DS200PTBAG1BBA are not detected correctly?
Troubleshooting should begin with the field device and follow the complete signal path toward the Mark V control system. Check the field sensor or signal source first, followed by terminal wiring, connector seating, cable continuity, and any associated shielding or grounding. The terminal assignment should also be compared with the original system drawings or documented wiring because an incorrect terminal connection can produce symptoms similar to a hardware failure. Jumper settings should be checked where applicable, as an incorrect configuration can change the expected signal behavior. If the field signal is confirmed to be correct but is still not reaching the control system, inspect the board connectors and associated downstream circuitry. This systematic approach helps distinguish between field device problems, wiring faults, configuration issues, and board-level failures.

6. What protection functions are associated with the DS200PTBAG1BBA?
The DS200PTBAG1BBA is associated with protection-related signal termination in the Mark V turbine control system. Applications can include overspeed protection and flame detection, along with other protective input circuits depending on the particular turbine configuration. Overspeed-related signals are especially important because they contribute to the protection system that responds when turbine rotational speed exceeds the permitted operating range. Flame detection signals can also be part of the protective logic used to monitor combustion conditions. Because the exact function of individual terminals depends on the turbine control configuration, technicians should always refer to the installed system wiring and control documentation when identifying a particular signal.

7. Why are the jumpers on the DS200PTBAG1BBA important?
Jumpers can be used to establish or modify specific hardware configuration conditions on the terminal board. Their function depends on the particular Mark V application and the circuit associated with the jumper location. Incorrect jumper positioning can change how a signal is routed or interpreted and may result in unexpected system behavior. For this reason, jumper positions should be recorded before removing an existing board and compared carefully with the replacement board during installation. Technicians should not change jumper settings simply to troubleshoot an unrelated signal problem unless the correct configuration has been established from the system documentation or the original board arrangement.

8. What checks should be performed after replacing the DS200PTBAG1BBA?
After replacement, the first step is to verify that the correct DS200PTBAG1BBA part number and revision are being installed for the specific Mark V system. All field wiring should then be checked against the documented terminal assignments, with particular attention to connectors, screw terminals, and jumper positions. The board should be inspected for loose connections or incorrectly seated plugs before power is restored. Once the system is energized under the approved commissioning procedure, the relevant input signals should be checked individually. Protection-related functions such as overspeed and flame detection should be tested according to the plant’s approved maintenance and commissioning procedures. Any associated alarms, permissives, and protective actions should also be verified before the turbine is returned to normal operation.

GE DS200PTBAG1BBA Mark V Terminal Board is in stock. Please contact us for a quick quote and competitive pricing.

Company Information
e-mail [email protected]
Mobile +8615305023276
Whatsapp +8615305023276
WeChat 13950166376
Add to Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China


Company Introduction

Xiamen Shengruite Trading Co., Ltd. is a company specializing in the supply of industrial PLC spare parts.

We provide high-quality PLC spare parts to customers in the global manufacturing, energy and power, chemical and other fields.

Since its establishment in 2011, after 13 years of rapid development, the cumulative global shipments have reached 223,650 pieces, with an annual output value of US$50 million.

Successfully served more than 500 customers in more than 100 countries and regions including Saudi Arabia, UAE, the United States, Europe, Africa, and Southeast Asia

Our Mission

Provide customers with the best quality PLC spare parts and the fastest delivery service to ensure that their industrial automation systems are always in the best operating condition.

Does this product come with a warranty?

We provide a 1-year warranty service, and we support returns and exchanges for any issues to ensure your rights and interests are fully protected.

How to Verify Products Before Purchase?

We can provide detailed product images upon request, and our team can arrange warehouse photos for confirmation to ensure you have all the information you need before making a purchase.

How long does shipping take?

Shipping times vary depending on your location. With the support of our 16 global warehouses, we strive to deliver orders as quickly as possible. Contact us to get an estimated delivery time for your specific location.

What is the minimum order quantity (MOQ)?

The minimum order quantity (MOQ) is typically one unit. However, for larger orders, please contact us for potential discounts and pricing details.

Can I get discounts for bulk purchases of products?

Yes, we offer competitive pricing for bulk purchases. Please reach out to our sales team with the specifics of your order to receive a custom quote.

What payment methods do you accept for wholesale orders?

We accept various payment methods for wholesale orders, including bank transfers (T/T), letters of credit, and other options upon agreement. For large transactions, please contact us directly for payment terms.

Can I purchase different quantities of a product?

Yes, we offer flexible ordering options for both small and large quantities. Whether youre looking for a single unit or a large batch, we can accommodate your needs.

Are there any discounts or promotions available for new wholesale customers?

We occasionally offer promotional discounts for new wholesale customers. Contact us to learn more about any current offers available for first-time buyers.

When purchasing a product, how can I ensure compatibility with my existing systems?

If you are unsure of compatibility with your existing setup please provide your system details and our support team can verify compatibility prior to purchase.

Can I return the goods I received if they do not meet our requirements?

Returns are accepted within 30 days if the product is unused, unopened, and in its original packaging. Please note that return shipping and associated costs are the buyer\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\’s responsibility.

Do you provide technical support or installation services to wholesale customers?

Yes, we offer technical support for the installation and integration of our products. Our team can assist with setup, configuration, and troubleshooting to ensure a smooth installation.