HIMA X-CB 001 02 985020008 Connector Board
| Company Information | ||||||||
| [email protected] | ||||||||
| Mobile | +8615305023276 | |||||||
| +8615305023276 | ||||||||
| 15305023276 | ||||||||
| Add to | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China | |||||||
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | HIMA |
| Model | X-CB 001 02 |
| Ordering Number | 985020008 |
| Product Type | HIMax Communication Module Connector Board |
| System | HIMax Programmable Electronic System (PES) |
| Compatible Module | X-COM 01 Communication Module |
| Main Function | Provides Ethernet and fieldbus connections for the X-COM 01 |
| Ethernet Interfaces | 4 × Ethernet |
| Ethernet Interface Identification | Eth1 (X3), Eth2 (X4), Eth3 (X5), Eth4 (X6) |
| Fieldbus Interfaces | 2 × Fieldbus |
| Fieldbus Interface Identification | FB1 (X1), FB2 (X2) |
| Fieldbus Function | Depends on the fieldbus submodules installed in the X-COM 01 |
| Module Connection | Plug-in connection |
| Installation Position | Corresponding slot on the HIMax base plate |
| System Configuration | X-CB 001 02 works together with X-COM 01 as a complete communication unit |
| Fieldbus Submodules | Not included with the connector board |
| Typical Applications | HIMax safety control systems, industrial Ethernet and fieldbus communication |
| Installation Requirement | The connector board should be installed before mounting the X-COM 01 |
| Dimensions | 300 × 15 × 30 mm |
| Weight | 0.2 kg |
FAQ
1. What is the main function of the HIMA X-CB 001 02?
The HIMA X-CB 001 02 is a communication connector board designed for the HIMax programmable electronic system. Its primary function is to provide the physical interface between the X-COM 01 communication module and external Ethernet and fieldbus networks. When installed together with the X-COM 01, it forms the complete communication interface required for connecting the HIMax system to external control systems, industrial networks, and field devices. The connector board provides the external connection points, while the X-COM 01 performs the actual communication processing and protocol functions. This separation allows the communication module to be maintained or replaced while minimizing the need to disturb external network wiring.
2. What is the difference between X-CB 001 02 and ordering number 985020008?
X-CB 001 02 is the model designation of the connector board, while 985020008 is its ordering number. Both identifiers should be used when purchasing, replacing, or managing spare parts to ensure the correct HIMA component is selected. The complete identification is therefore HIMA X-CB 001 02, Ordering Number 985020008. When replacing the board in an existing HIMax installation, technicians should verify the complete product identification rather than selecting a similar-looking connector board based only on its physical appearance or number of interfaces.
3. What communication interfaces are available on the X-CB 001 02?
The X-CB 001 02 provides two main groups of communication interfaces: four Ethernet interfaces and two fieldbus interfaces. The Ethernet connections are identified as Eth1 (X3), Eth2 (X4), Eth3 (X5), and Eth4 (X6). The fieldbus interfaces are identified as FB1 (X1) and FB2 (X2). The actual fieldbus communication standard available through FB1 and FB2 depends on the fieldbus submodules installed in the associated X-COM 01. These interfaces allow the HIMax communication module to connect to external industrial Ethernet networks and compatible fieldbus devices.
4. Can the X-CB 001 02 be used independently without an X-COM 01?
The X-CB 001 02 is primarily designed as the connector board for the X-COM 01 and does not provide the complete communication processing functionality by itself. The HIMA system architecture uses the X-CB 001 02 and X-COM 01 together as a complete communication unit. The connector board provides the physical external interfaces, while the X-COM 01 handles communication protocols, data processing, and related diagnostic functions. Therefore, installing the connector board alone cannot replace an X-COM 01 communication module. For a complete communication interface, the appropriate X-COM 01 configuration must be installed together with the connector board.
5. How should the X-CB 001 02 be installed with the X-COM 01?
The X-CB 001 02 should first be correctly installed in the designated position on the HIMax base plate before the X-COM 01 communication module is mounted. Once the connector board is securely installed, the X-COM 01 can be fitted into its corresponding position so that the module and connector board interfaces engage correctly. During installation, care should be taken to avoid excessive mechanical force on connectors and contacts. The module should be fully seated and securely fixed according to the HIMax installation procedure. One practical advantage of this arrangement is that when the X-COM 01 needs to be replaced, the external Ethernet and fieldbus wiring connected to the connector board can normally remain in place.
6. Should the X-CB 001 02 be checked if all Ethernet communication from the X-COM 01 fails?
Yes. If multiple Ethernet interfaces on the X-COM 01 fail simultaneously, the X-CB 001 02 should be included in the troubleshooting process. First verify that the connector board is correctly installed on the HIMax base plate and that the Ethernet connectors are properly seated. The Eth1 through Eth4 connections, network cables, and external network equipment should also be inspected. If all Ethernet ports are affected at the same time, the X-COM 01 operating status, system bus, and power conditions should also be checked. If only one Ethernet interface is affected, attention should initially be focused on the corresponding connector, cable, and external communication device. This approach helps distinguish a connector-board or module problem from an external network fault.
7. Can the fieldbus interfaces on the X-CB 001 02 be used directly?
The X-CB 001 02 provides the FB1 and FB2 fieldbus connection points, but actual fieldbus communication depends on the appropriate fieldbus submodules being installed in the associated X-COM 01. Without the required fieldbus hardware, the corresponding interface cannot provide the intended fieldbus communication function. The installed submodule determines the supported communication standard and interface configuration. When using FB1 or FB2, the hardware configuration of the X-COM 01 should therefore be checked first. If Ethernet communication is operating normally but a fieldbus connection cannot be established, troubleshooting should focus on the fieldbus submodule, protocol configuration, field wiring, and the connected fieldbus device.
8. What should be considered when replacing the X-CB 001 02?
When replacing the X-CB 001 02, first verify that the replacement component has the correct identification: X-CB 001 02 985020008. Compatibility with the installed X-COM 01 and HIMax base plate should also be confirmed. Before maintenance, the HIMax system should be placed into the appropriate maintenance or safe state according to the site’s procedures, and required power isolation should be performed. During removal, protect the Ethernet and fieldbus connectors as well as the connection between the board and the base plate. After installing the replacement connector board, verify that all connections are secure before mounting the X-COM 01. Once the system is restarted, check Ethernet link status, fieldbus status, and HIMax diagnostic information. For safety-related applications, complete communication and system-function testing should be performed before returning the system to normal operation.
HIMA X-CB 001 02 985020008 Connector Board is in stock. Please contact us for a quick quote and competitive pricing.
| Company Information | ||||||||
| [email protected] | ||||||||
| Mobile | +8615305023276 | |||||||
| +8615305023276 | ||||||||
| 13950166376 | ||||||||
| Add to | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China | |||||||
Company Introduction
Xiamen Shengruite Trading Co., Ltd. is a company specializing in the supply of industrial PLC spare parts.
We provide high-quality PLC spare parts to customers in the global manufacturing, energy and power, chemical and other fields.
Since its establishment in 2011, after 13 years of rapid development, the cumulative global shipments have reached 223,650 pieces, with an annual output value of US$50 million.
Successfully served more than 500 customers in more than 100 countries and regions including Saudi Arabia, UAE, the United States, Europe, Africa, and Southeast Asia
Our Mission
Provide customers with the best quality PLC spare parts and the fastest delivery service to ensure that their industrial automation systems are always in the best operating condition.
We provide a 1-year warranty service, and we support returns and exchanges for any issues to ensure your rights and interests are fully protected.
We can provide detailed product images upon request, and our team can arrange warehouse photos for confirmation to ensure you have all the information you need before making a purchase.
Shipping times vary depending on your location. With the support of our 16 global warehouses, we strive to deliver orders as quickly as possible. Contact us to get an estimated delivery time for your specific location.
The minimum order quantity (MOQ) is typically one unit. However, for larger orders, please contact us for potential discounts and pricing details.
Yes, we offer competitive pricing for bulk purchases. Please reach out to our sales team with the specifics of your order to receive a custom quote.
We accept various payment methods for wholesale orders, including bank transfers (T/T), letters of credit, and other options upon agreement. For large transactions, please contact us directly for payment terms.
Yes, we offer flexible ordering options for both small and large quantities. Whether youre looking for a single unit or a large batch, we can accommodate your needs.
We occasionally offer promotional discounts for new wholesale customers. Contact us to learn more about any current offers available for first-time buyers.
If you are unsure of compatibility with your existing setup please provide your system details and our support team can verify compatibility prior to purchase.
Returns are accepted within 30 days if the product is unused, unopened, and in its original packaging. Please note that return shipping and associated costs are the buyer\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\’s responsibility.