Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | ABB |
| Model | RET670 |
| Ordering Number | 1MRK004816-BC |
| Product Type | Transformer Protection Relay |
| Product Series | ABB Relion 670 Series |
| Main Application | Protection, control, measurement and supervision of power transformers |
| Typical Applications | Two-winding and three-winding transformers, autotransformers, generator-transformer units and transmission/substation transformers |
| Core Protection Function | Transformer differential protection |
| Differential Protection | Fast low-impedance differential protection for transformer internal faults |
| Inrush Restraint | Harmonic-based inrush restraint to improve security during transformer energization |
| Backup Protection | Phase overcurrent and residual/earth-fault overcurrent protection |
| Earth-Fault Protection | Instantaneous and multi-stage residual overcurrent protection |
| Thermal Protection | Thermal overload protection and transformer thermal monitoring |
| CT Inputs | 1 A or 5 A rated current inputs |
| CT Nominal Range | Approximately 0.2–40 × Ir, depending on the transformer input module |
| CT Continuous Overload | Up to 4 × Ir continuous |
| CT Short-Time Overload | Up to 100 × Ir for 1 second under specified conditions |
| VT Inputs | Nominal 110 V typical; operating range depends on the installed analog module |
| VT Operating Range | Up to approximately 340 V under specified conditions |
| Rated Frequency | 50 / 60 Hz |
| Binary Inputs | 8 inputs per standard IOM module; total quantity depends on the selected hardware configuration |
| Binary Outputs | 10 trip/signal relays plus 2 fast signal relays per standard IOM module |
| PLC / Programmable Logic | Integrated programmable logic for interlocking, control and automation |
| Measurement Functions | Current, voltage, frequency, power and other electrical quantities according to configuration |
| Event Recording | Protection and operational event recording |
| Disturbance Recording | Fault and disturbance waveform recording for post-event analysis |
| Self-Supervision | Internal hardware and software diagnostics |
| Communication | Serial and Ethernet communication interfaces depending on configuration |
| Communication Protocols | IEC 61850, LON, SPA, DNP3 and IEC 60870-5-103, depending on installed communication options |
| IEC 61850 | Supported for substation automation integration |
| Time Synchronization | External time synchronization supported according to communication configuration |
| Local HMI | Graphical display and keypad-based local operation |
| Auxiliary Power | Configuration-dependent AC/DC auxiliary power supply |
| Installation | Panel mounting, flush mounting or 19-inch rack installation |
| Typical Operating Temperature | Approximately -25 to +55 °C, depending on hardware configuration |
| Dimensions | 265.9 × 223.7 × 242.1 mm |
| Weight | 10 kg |
FAQ
1. What is the ABB RET670 1MRK004816-BC used for?
The ABB RET670 is a dedicated transformer protection and control IED designed for protecting power transformers and associated high-voltage equipment. It combines transformer differential protection with backup overcurrent, earth-fault, thermal and monitoring functions. Depending on the configuration, it can be applied to two-winding or three-winding transformer arrangements and can also be integrated into generator-transformer and substation protection systems. The combination of protection, measurement, programmable logic and communication functions allows the RET670 to perform as part of a complete transformer protection and automation scheme.
2. What is the main protection function of the RET670?
The main protection function is fast transformer differential protection. The relay compares currents from the different transformer sides and determines whether the measured current difference corresponds to an internal transformer fault. This provides rapid protection against faults such as winding short circuits and phase-to-phase faults within the protected zone. The differential protection can be coordinated with other protection elements so that internal faults are cleared quickly while external faults remain stable.
3. How does RET670 prevent transformer inrush current from causing false trips?
Transformer energization can produce a high magnetizing inrush current that may appear similar to an internal fault. The RET670 uses restraint and recognition techniques, including harmonic-based inrush restraint, to distinguish transformer energization conditions from genuine internal faults. This improves protection security during transformer switching operations. Correct CT characteristics, transformer data, vector-group settings and differential protection parameters are still essential because incorrect configuration can reduce the reliability of the differential protection scheme.
4. What CT specifications are supported by the RET670?
The RET670 transformer protection input modules support CT secondary ratings of 1 A or 5 A. Depending on the installed transformer input module, the current operating range can extend significantly above the rated current, with specified continuous and short-time overload capabilities. Correct CT ratio, polarity, phase sequence, wiring and burden are particularly important for differential protection. When commissioning a RET670, the CT connections on every transformer side should be checked carefully because incorrect polarity or phase assignment can create an artificial differential current.
5. Can the RET670 be used for three-winding transformer protection?
Yes. RET670 configurations can be used for three-winding transformer protection as well as two-winding applications. The relay can process current information from the relevant transformer sides and perform differential calculations according to the configured protection scheme. For a three-winding transformer, engineering must correctly define CT ratios, transformer winding connections, phase compensation, grounding arrangements and protected zones. The exact number of analog inputs and protection functions depends on the hardware and configuration associated with the particular ordering code.
6. What backup protection functions are available in the RET670?
In addition to differential protection, RET670 can provide phase overcurrent and residual overcurrent protection. Multi-stage overcurrent functions allow separate operating levels and time delays to be configured for different fault conditions. Earth-fault protection can provide backup protection for faults that may not be cleared by the primary differential element. Thermal protection and transformer monitoring functions can also contribute to overall equipment protection by detecting prolonged overload conditions and abnormal operating states.
7. Does the ABB RET670 support IEC 61850 and substation automation?
Yes. The RET670 platform supports integration with modern substation automation systems, including IEC 61850 communication when the appropriate communication configuration is installed. Depending on the hardware and software options, other protocols such as LON, SPA, DNP3 and IEC 60870-5-103 can also be supported. Communication can be used to transfer protection status, measurements, alarms, events and control information between the relay and higher-level automation or SCADA systems. IEC 61850 also provides a practical architecture for integrating protection IEDs into digital substation networks.
8. How should a RET670 be troubleshot when differential protection operates unexpectedly?
The first step is to review the relay event records, disturbance records and internal diagnostic information to determine which protection element operated and what current values were measured. The CT secondary circuits should then be checked for correct ratio, polarity, phase sequence, wiring and continuity. Transformer vector-group and compensation settings should also be verified against the actual transformer nameplate and engineering documentation. If the differential current appears only during energization, the inrush restraint settings and transformer switching conditions should be examined. Communication faults should be checked separately by verifying the communication module, network connection, protocol settings and station configuration. Hardware replacement should normally be considered only after external wiring and configuration have been confirmed to be correct.
ABB RET670 1MRK004816-BC Transformer Protection Relay is in stock. Please contact us for a quick quote and competitive pricing.
| Company Information | ||||||||
| [email protected] | ||||||||
| Mobile | +8615305023276 | |||||||
| +8615305023276 | ||||||||
| 13950166376 | ||||||||
| Add to | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China | |||||||
Company Introduction
Xiamen Shengruite Trading Co., Ltd. is a company specializing in the supply of industrial PLC spare parts.
We provide high-quality PLC spare parts to customers in the global manufacturing, energy and power, chemical and other fields.
Since its establishment in 2011, after 13 years of rapid development, the cumulative global shipments have reached 223,650 pieces, with an annual output value of US$50 million.
Successfully served more than 500 customers in more than 100 countries and regions including Saudi Arabia, UAE, the United States, Europe, Africa, and Southeast Asia
Our Mission
Provide customers with the best quality PLC spare parts and the fastest delivery service to ensure that their industrial automation systems are always in the best operating condition.
We provide a 1-year warranty service, and we support returns and exchanges for any issues to ensure your rights and interests are fully protected.
We can provide detailed product images upon request, and our team can arrange warehouse photos for confirmation to ensure you have all the information you need before making a purchase.
Shipping times vary depending on your location. With the support of our 16 global warehouses, we strive to deliver orders as quickly as possible. Contact us to get an estimated delivery time for your specific location.
The minimum order quantity (MOQ) is typically one unit. However, for larger orders, please contact us for potential discounts and pricing details.
Yes, we offer competitive pricing for bulk purchases. Please reach out to our sales team with the specifics of your order to receive a custom quote.
We accept various payment methods for wholesale orders, including bank transfers (T/T), letters of credit, and other options upon agreement. For large transactions, please contact us directly for payment terms.
Yes, we offer flexible ordering options for both small and large quantities. Whether youre looking for a single unit or a large batch, we can accommodate your needs.
We occasionally offer promotional discounts for new wholesale customers. Contact us to learn more about any current offers available for first-time buyers.
If you are unsure of compatibility with your existing setup please provide your system details and our support team can verify compatibility prior to purchase.
Returns are accepted within 30 days if the product is unused, unopened, and in its original packaging. Please note that return shipping and associated costs are the buyer\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\’s responsibility.
Yes, we offer technical support for the installation and integration of our products. Our team can assist with setup, configuration, and troubleshooting to ensure a smooth installation.