Bently Nevada 3500/65-01-01 16-Channel Temperature Monitor
| Company Information | ||||||||
| [email protected] | ||||||||
| Mobile | +8615305023276 | |||||||
| +8615305023276 | ||||||||
| 15305023276 | ||||||||
| Add to | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China | |||||||
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 3500/65-01-01 |
| Product Type | 16-Channel Temperature Monitor |
| Product Series | 3500 Series |
| Number of Monitoring Channels | 16 |
| Input Types | RTD and Isolated Thermocouple (TC) |
| RTD Type | 3-Wire RTD, 4-Wire RTD |
| Thermocouple Types | E, J, K, T |
| Number of Inputs | 1–16 RTD or Isolated TC Inputs |
| Input Impedance | >1 MΩ per input |
| RTD Excitation Current | 913 ± 7 μA at 25°C |
| Measurement Resolution | 1°C or 1°F |
| Measurement Accuracy | ±3°C at 25°C |
| Cold Junction Compensation Accuracy | ±2°C at 25°C |
| Signal Processing | Input conditioning and temperature measurement |
| Alarm Functions | Alert and Danger |
| Alarm Setpoint Range | 0–100% of Full Scale |
| Alarm Types | High and Low |
| Alarm Delay | Software configurable |
| Configuration Software | 3500 Rack Configuration Software |
| Front Panel Indicators | OK, TX/RX, Bypass |
| Power Consumption | 3 W typical |
| Operating Temperature | -30°C to +65°C |
| Storage Temperature | -40°C to +85°C |
| Installation | 3500 Rack, one full-height slot |
| TMR Support | Yes, using three adjacent temperature monitors |
| E-Type Thermocouple Range | -100°C to +1000°C |
| J-Type Thermocouple Range | 0°C to +760°C |
| K-Type Thermocouple Range | 0°C to +1370°C |
| T-Type Thermocouple Range | -160°C to +400°C |
| Dimensions | 241.3 × 24.4 × 241.8 mm |
| Weight | 0.91 kg |
FAQ
1. What is the primary function of the Bently Nevada 3500/65-01-01?
The 3500/65-01-01 is a 16-channel temperature monitor designed for temperature measurement and monitoring within the Bently Nevada 3500 machinery protection system. It accepts temperature signals from RTD sensors and isolated thermocouples and processes these signals for continuous equipment monitoring. Typical applications include radial bearing temperature, thrust bearing temperature, compressor inlet and discharge temperature, steam temperature, motor stator temperature, and other critical machine or process temperature points. The monitor can compare measured temperatures with configured Alert and Danger setpoints. When an abnormal temperature condition is detected, the temperature status can be used by the broader 3500 protection system for alarm, relay, or shutdown functions.
2. What types of temperature sensors are supported by the 3500/65-01-01?
The 3500/65-01-01 supports RTD and isolated thermocouple temperature inputs. RTD applications can use 3-wire or 4-wire configurations, while supported thermocouple types include E, J, K, and T. Up to 16 temperature channels can be configured according to the requirements of the monitoring application. Each channel must be configured to match the actual sensor installed in the field. For example, selecting a K-type thermocouple configuration when a J-type sensor is installed can result in significant measurement errors. Correct sensor selection, wiring, polarity, and software configuration are therefore essential for reliable temperature measurement.
3. How many temperature points can the 3500/65-01-01 monitor?
The 3500/65-01-01 can monitor up to 16 temperature input channels simultaneously. The available channels can be assigned to different temperature measurement points depending on the machine and monitoring requirements. For large rotating machinery, individual channels can be used for radial bearings, thrust bearings, motor windings, process temperatures, or other critical locations. Each input should be clearly identified during installation so that the channel number corresponds to the correct physical measurement point. Proper channel identification is especially important in machinery protection systems because an incorrect channel assignment could cause maintenance personnel or operators to associate an alarm with the wrong equipment location.
4. How does the 3500/65-01-01 temperature alarm function work?
The 3500/65-01-01 supports Alert and Danger temperature alarm functions. Alarm setpoints can be configured through the 3500 Rack Configuration Software according to the temperature range and protection requirements of each measurement point. High and low temperature alarm conditions can be configured, and alarm delays can be used to prevent short-duration temperature fluctuations from causing unnecessary alarms. The temperature monitor performs the measurement and alarm evaluation, while the complete 3500 machinery protection system can use the resulting status for additional relay, alarm, or shutdown functions. Alarm values should be selected according to the actual machine manufacturer’s limits and operating conditions rather than using the same setpoint for every temperature channel.
5. Does the 3500/65-01-01 support TMR redundant operation?
Yes. The 3500/65 temperature monitoring system can be used in a Triple Modular Redundant (TMR) configuration. A TMR arrangement uses three temperature monitors installed in adjacent rack positions to improve system availability and reliability. Redundant monitoring allows the protection system to continue operating even if one monitoring module develops a fault, depending on the overall system architecture and voting configuration. TMR is particularly useful for critical rotating machinery where a single module failure should not unnecessarily interrupt the protection function. When designing a TMR system, the temperature monitors, I/O configuration, rack arrangement, system software, and redundancy logic should all be configured consistently.
6. How should an abnormal temperature reading on the 3500/65-01-01 be troubleshot?
Troubleshooting should begin with the temperature sensor and field wiring before assuming that the temperature monitor has failed. First, verify that the sensor type configured for the affected channel matches the actual RTD or thermocouple installed in the machine. Then inspect the RTD wiring configuration, thermocouple polarity, terminal connections, cable condition, and signal continuity. Open circuits, short circuits, poor connections, damaged extension cables, or incorrect sensor polarity can all produce abnormal temperature readings. If the field wiring is correct, review the channel configuration, measurement range, and alarm settings in the 3500 configuration software. Comparing the affected channel with other known-good channels can help determine whether the problem follows the sensor or remains associated with a particular input channel. The monitor hardware should normally be considered only after the sensor, wiring, and configuration have been verified.
7. Can the 3500/65-01-01 be integrated with a PLC or DCS?
Yes. The 3500/65-01-01 operates as part of the 3500 machinery protection system, and temperature measurement and alarm information can be integrated with PLC, DCS, HMI, and other automation systems through the appropriate 3500 system interfaces. In a typical industrial installation, the 3500 system provides dedicated machinery monitoring and protection functions, while the PLC or DCS handles process control, operator monitoring, and higher-level data management. During integration, the engineering team should clearly define the relationship between temperature values, Alert status, Danger status, channel faults, and machine protection signals. Proper configuration of these signals is important to prevent nuisance trips while ensuring that genuine high-temperature conditions receive the required response.
8. What should be checked before replacing a 3500/65-01-01?
Before replacing the 3500/65-01-01, the fault should first be isolated to the temperature monitor rather than the sensor, field wiring, I/O configuration, or another part of the 3500 system. Check the affected temperature channels and compare their behavior with other functioning channels. Inspect the RTD or thermocouple wiring, verify the configured sensor type, and review the relevant alarm and module status information. The existing configuration and channel settings should be recorded before replacement so that the replacement monitor can be configured consistently. After installing the replacement module, verify that it is properly seated in the 3500 rack and check the OK, TX/RX, and Bypass indicators. Finally, verify the temperature readings, channel status, alarm conditions, and system communication for all required channels before returning the machinery protection system to normal operation.
Bently Nevada 3500/65-01-01 16-Channel Temperature Monitor is in stock. Please contact us for a quick quote and competitive pricing.
| Company Information | ||||||||
| [email protected] | ||||||||
| Mobile | +8615305023276 | |||||||
| +8615305023276 | ||||||||
| 13950166376 | ||||||||
| Add to | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China | |||||||
Company Introduction
Xiamen Shengruite Trading Co., Ltd. is a company specializing in the supply of industrial PLC spare parts.
We provide high-quality PLC spare parts to customers in the global manufacturing, energy and power, chemical and other fields.
Since its establishment in 2011, after 13 years of rapid development, the cumulative global shipments have reached 223,650 pieces, with an annual output value of US$50 million.
Successfully served more than 500 customers in more than 100 countries and regions including Saudi Arabia, UAE, the United States, Europe, Africa, and Southeast Asia
Our Mission
Provide customers with the best quality PLC spare parts and the fastest delivery service to ensure that their industrial automation systems are always in the best operating condition.
We provide a 1-year warranty service, and we support returns and exchanges for any issues to ensure your rights and interests are fully protected.
We can provide detailed product images upon request, and our team can arrange warehouse photos for confirmation to ensure you have all the information you need before making a purchase.
Shipping times vary depending on your location. With the support of our 16 global warehouses, we strive to deliver orders as quickly as possible. Contact us to get an estimated delivery time for your specific location.
The minimum order quantity (MOQ) is typically one unit. However, for larger orders, please contact us for potential discounts and pricing details.
Yes, we offer competitive pricing for bulk purchases. Please reach out to our sales team with the specifics of your order to receive a custom quote.
We accept various payment methods for wholesale orders, including bank transfers (T/T), letters of credit, and other options upon agreement. For large transactions, please contact us directly for payment terms.
Yes, we offer flexible ordering options for both small and large quantities. Whether youre looking for a single unit or a large batch, we can accommodate your needs.
We occasionally offer promotional discounts for new wholesale customers. Contact us to learn more about any current offers available for first-time buyers.
If you are unsure of compatibility with your existing setup please provide your system details and our support team can verify compatibility prior to purchase.
Returns are accepted within 30 days if the product is unused, unopened, and in its original packaging. Please note that return shipping and associated costs are the buyer\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\’s responsibility.